Three phase Input +
Three phase Output

ONLINE UPS is one type of Uninterruptable Power Supply that provides continuous power supply to critical equipment & system by constantly converting incoming AC power to DC power and then back to AC power. It Provides protection against any type of power failures i.e. Power Surge, Voltage reregulation, Brownout, complete Blackout and it’s help to give consistent power supply to the system.
  • Process Industries
  • Manufacturing Industries
  • Research Laboratories
  • Data Centers & Server Rooms
  • Medical & Healthcare Units
  • Telecommunication Network
  • Financial & Educational Institute

Technical Specification

Make COSMIC+®
Model No. MS+303U
Input Phase 3 phase + N + E
Rating in KVA 10 KVA to 200 KVA
Rated Input voltage 415 V ± 10%, AC Single Phase
Input Frequency 50/60 Hz
Output Phase 3 phase + N + E
Rated output voltage 380 / 400 / 415V ± 1%, AC Three Phase
Output voltage regulation from no-load to full load ± 1%
Frequency stability 50Hz ± 0.1Hz
Transient response time Around 40msec
Inverter efficiency > 93 %
Overload time (without bypass) in Sec. for 110% for 5 mins & 150% for 60 Sec
Output wave form PWM Sine wave
Total Harmonic distortion for Less than 3%
Crest factor 3:1
Phase displacement 120º ± 1º
Output Power factor 0.8
Technology DSP based, IGBT Switching Double conversion
Transformer insulation Inbuilt Copper/Aluminium Isolation transformer
Type of metering LCD / Digital type / LED
Cooling method Fan cooling
Cable entry (Incoming & Outgoing) Bottom Rear side
Colour shade Powder Coating – Black / Gray Met finish
Degree of protection for panel Enclosure IP 20
Audible noise at 1 mtr. Distance Less than 50 dB
DC Bus voltage 360 VDC / 384 VDC
Type of battery SMF
Voltage rating & No. of batteries 12 V & 30 Nos. / 32 nos.
Recharge time up to 100% capacity 12 hours
Make of the Batteries Exide / Amaron or equivalent
Type of Communication SNMP communication port (on request)
Type of Bypass Manual bypass switch / Static bypass on request
Digital Display
R, Y, B Input and Output Voltages, Output currents & Frequency, DC Voltage, Battery and Load Percentage and All Faults
Protection
Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage, Mains Under & Overvoltage, Mains Single Phasing.
Site Conditions
Maximum ambient temperature 40° C
Minimum ambient temperature 5° C
Design temperature 40° C
Humidity 95% RH
Altitude Less than 1000m above mean sea level
Type of Earthing Solid Chemical earthing required